DP-P Series MULTIFUNCTIONAL LABORATORY POWER SUPPLIES

Maximum ratings for the series (depending on the model): 2000 V / 1000 A / 15 kW / ØPL = 0.85 €/W

Output and Control Quality Functions and Interfaces
Voltage range: 0 ... 2kV Master/Slave Parallel Operation: Yes, only for 15-kW modules
Current range: 0 … 1000 A Master/Slave serial operation: No
Power range: 0 ... 15kW Remote Sensing: Up to 2 V at a rated current exceeding 50 A
Cabinet: 19″ 2U half-width (-S)
19″ 2U / 3U full-width, depending on the model
RS232: Yes
Regulation: CV / CC RS485: Yes
Output to PE: Up to 1,500 V potential-free
; above that, grounded
RS422: No
Setting accuracy U: ±0.2% ± 2 LSB USB: No
Setting accuracy I: ±0.5% ± 2 LSB LAN: Yes*
Display accuracy U: ≤0.2% ± 2 LSB Analog Control: Yes*
Display accuracy I: ≤0.5% ± 2 LSB Analog actual value outputs: Yes*
Load regulation U: Per model: ≤0.1% + 2 LSB
to ≤0.21% + 2 LSB
Modbus RTU: Yes
Load regulation I: Per model: ≤0.1% + 2 LSB
to ≤0.2% + 2 LSB
SCPI: No
Mains regulation U: ≤0.1% + 2 LSB Interlock: Yes
Line regulation I: ≤0.1% + 2 LSB External Output On/Off: Yes*
Residual ripple U: ≤50 … ≤200 mVpp, depending on the model Reverse current protection: Integrated, same-pole
Residual Ripple I: ≤50 … ≤200 mApp, depending on the model
Individual models: ≤50 mArms
Polarity changer: External Module AP6*
Recovery time: Not specified AP Expansion Modules: AP5 through AP9*

 

Output and Design
Voltage range: 0 ... 2kV
Current range: 0 … 1000 A
Power range: 0 ... 15kW
Cabinet: 19″ 2U half-width (-S)
19″ 2U / 3U full-width, depending on the model
Regulation: CV / CC
Output to PE: Up to 1,500 V potential-free
; above that, grounded
Functions and Interfaces
Master/Slave Parallel Operation: Yes, only for 15-kW modules
Master/Slave serial operation: No
Remote Sensing: Up to 2 V at a rated current exceeding 50 A
RS232: Yes
RS485: Yes
RS422: No
USB: No
LAN: Yes*
Analog Control: Yes*
Analog actual value outputs: Yes*
Modbus RTU: Yes
SCPI: No
Interlock: Yes
External Output On/Off: Yes*
Reverse current protection: Integrated, same-pole
Polarity changer: External Module AP6*
AP Expansion Modules: AP5 through AP9*
Control Quality
Setting accuracy U: ±0.2% ± 2 LSB
Setting accuracy I: ±0.5% ± 2 LSB
Display accuracy U: ≤0.2% ± 2 LSB
Display accuracy I: ≤0.5% ± 2 LSB
Load regulation U: Per model: ≤0.1% + 2 LSB
to ≤0.21% + 2 LSB
Load regulation I: Per model: ≤0.1% + 2 LSB
to ≤0.2% + 2 LSB
Mains regulation U: ≤0.1% + 2 LSB
Line regulation I: ≤0.1% + 2 LSB
Residual ripple U: ≤50 … ≤200 mVpp, depending on the model
Residual Ripple I: ≤50 … ≤200 mApp, depending on the model
Individual models: ≤50 mArms
Recovery time: Not specified

* Optional. The overview summarizes various models. If equipped with analog I/O, RS232 is not included. "pp" refers to peak-to-peak values, and "rms" refers to the root mean square value.

The DP-P Series DC laboratory power supplies offer a wide range of models for development workstations, automated test benches, and industrial power supply applications. The digital control loop, based on ARM architecture, continuously monitors the output values and automatically switches between constant-voltage and constant-current (CV/CC) modes depending on the load.

Operate your power supply directly from the front panel or integrate it into your existing infrastructure. RS232 and RS485 with Modbus RTU are included. An optional LAN interface with server/client operation is available, as well as an independent analog I/O package that replaces RS232 and enables the control of voltage and current, as well as the feedback of both actual values via 0 … 5V, 0 … 10V, or 4 … 20mA.

The documented Modbus RTU protocol simplifies integration into custom control solutions, such as those using LabVIEW.

The 15-kW modules in the DP-P series support " Master/Slave" parallel operation as standard and are available in " Master" or "Slave" versions. Models with different rated power do not support this feature. " Master/Slave" operation is possible only in parallel configuration and not in series configuration.

An overview of the advantages of the DP-P Series multifunction laboratory power supplies:

Connectivity RS485 and RS232 with support for Modbus RTU. Optional LAN with configurable server/client operation and, independently of this, an analog I/O package for voltage and current control, as well as both actual value outputs with 0 … 5 V, 0 … 10 V, or 4 … 20 mA instead of RS232. 5-V status output and interlock via a 5-V loop.
Features Output values from 0 to 100% are variably adjustable. Constant-voltage and constant-current operation with automatic switching depending on the load. Remote measurement input for compensating for line losses up to 2 V on models with an output current exceeding 50 A.
Output configuration Master-output on models with an output voltage up to 1,500 V. Short-circuit-proof and suitable for continuous operation in short-circuit mode. The 15-kW modules support /slave parallel operation as standard and are available in Master or slave versions. Models with other rated powers do not support Master/slave parallel operation. Two units can also be operated as a bipolar voltage source with grounding at the center.
Security Automatic shutdown in case of overtemperature, overvoltage, and overcurrent, with a fault indicator. The front panel can be deactivated or locked. The output can be blocked or enabled via the interlock loop.
Upgrade options Compatible with the AP9, AP8, AP7, AP6, and AP5 external expansion modules for reverse current protection, additional EMC filtering, polarity reversal, and mechanical load isolation.

*Optional

Format and performance

Multifunctional laboratory power supplies of the DP-P Series in various versions

Image shows DP-P series laboratory power supplies, please refer to the data sheet for the size of the selected model.

The temperature-dependent fan control adjusts cooling based on output parameters and operating conditions. Depending on the model, the units can be used as freestanding units or mounted in a rack. While rack mounts are included with full-width units, a shared rack slot for two half-width units is available separately.

600W models and models rated at 1200W with the suffix -S 19-inch half-width, 2U; 21.3 cm wide, 8.8 cm high, 34 cm deep
Full-width models up to and including 5 kW 19-inch full-width, 2U; depth varies by model
Full-width models starting at 6 kW 19-inch full-width, 3U; depth varies by model

This classification describes the currently listed standard models. Not every 1200W model is a half-width unit. The half-width version can be identified by the suffix -S. For special versions and installation planning, the confirmed model dimensions are authoritative.

Greater Performance in Parallel Operation

If a single power supply unit is not sufficient, expand your DC power supply with a Master/Slave parallel system consisting of 15-kW modules from the DP-P series. The voltage range remains the same, while the available current increases with the number of modules. The following example systems range from 30 V to 2,000 V and each provide more current than a single standard model in the series can deliver at the specified voltage.

For each voltage range shown, the examples use six identical 15-kW modules. The maximum output voltage, total current, and calculated system power are listed. One unit is configured as the " Master " [M1], and the other five as "Slaves" [M2]. DP-P models with different rated power do not support " Master" / "Slave" parallel operation.

DP-P Series: Sample systems, each with six 15-kW modules
Max. System Voltage Max. Total Current Max. System Performance* Performance Modules Equipment height in a 19-inch rack
30V 3000A 90 kW 6 × DP30-5HP 18HE
60V 1500A 90 kW 6 × DP60-250P 18HE
100V 900A 90 kW 6 × DP1H-150P 18HE
200V 450A 90 kW 6 × DP2H-75P 18HE
300V 300A 90 kW 6 × DP3H-50P 18HE
600V 150A 90 kW 6 × DP6H-25P 18HE
1000V 90A 90 kW 6 × DP10H-15P 18HE
1500V 60A 90 kW 6 × DP15H-10P 18HE
2000V 45A 90 kW 6 × DP20H-7-5P 18HE

* System power is calculated based on the listed voltage and current limits and is capped at the sum of the modules' rated powers. The HE specification covers only the equipment heights; therefore, additional space for cooling, cabling, and protective components must be planned for separately.

We tailor the number of modules, system configuration, grid connection, and protective circuitry to your test setup. For loads that feed energy back into the grid, a properly designed protection concept is required.

Full control

DP-P Series Multifunctional Laboratory Power Supplies Software Suite

Image shows a screenshot from the software suite for DP-P and DP-PH series laboratory power supplies.

The DP-P Series was developed with a focus on high-performance laboratory applications that demand a high degree of precision and automation. The devices come with a comprehensive software suite for Windows 10 and 11. It allows users to set and monitor output values as well as program repetitive voltage and current waveforms. Connectivity is provided via RS485 or RS232 with Modbus RTU, as well as optionally via LAN. When equipped with analog I/O, RS232 is not available.

Compatible with many external expansion modules of the AP series

Expand your laboratory power supply of the DP-P series with additional functions – even after purchase.

Image shows a DP-M series high-performance power supply unit in 2U cabinet with AP8 module (top).

The DP-P Series is compatible with the AP9, AP8, AP7, AP6, and AP5 external expansion modules. The required electrical and mechanical specifications are tailored to the power supply, load, and test setup prior to ordering.

Integrated reverse current protection and additional protection modules
The output rectifier stage provides basic protection against reverse currents of the same polarity within the device’s permissible limits. This does not imply unlimited reverse current capability or suitability for absorbing arbitrary load energy. Reverse voltages, high reverse currents, and the stored energy of the load must be taken into account during design.

Model AP9: Application-Specific Reverse Current and Reverse Voltage Protection
The AP9 complements the integrated protection for demanding inductive or capacitive loads. The module is designed to order for the expected currents, voltages, and energy levels. Depending on the application, a combined protection circuit against high reverse currents and reverse voltages—particularly against reverse-polarity transients—or a design as an active braking chopper is possible. A braking chopper limits the energy fed back into the system by converting it into heat. The design, sizing, and permissible duty cycles are agreed upon on a case-by-case basis.

Model AP8: Additional output-side EMC filter with capacitance
AP8 combines a three-stage EMC filter with additional output capacitance. It serves to further reduce line-borne interference and stabilize the power supply to demanding loads. The design is tailored to the power supply unit, load, and dynamic requirements.

Model AP7: Additional input-side EMC filter
The AP7 supplements the existing power supply filtering with a three-stage EMC filter. It is designed for applications with increased requirements for reducing conducted interference on the power supply side. The single- or three-phase configuration and current-carrying capacity are selected to match the power supply unit.

Model AP6: Polarity Reverser
The AP6 allows the output polarity to be switched either at the module or via an external control loop. Before each polarity change, interrupt the load current—for example, by turning off the output or using an existing interlock function. Current-free switching is not automatically guaranteed. The electrical and mechanical design is tailored to the power supply and the application.

Model AP5: Mechanical Isolation of the Load
The AP5 provides mechanical isolation between the power supply and the load or test bench. It supplements the electronic output control with a physical isolation point designed for specific applications. The specific protective effect depends on the overall safety concept of the system.

All AP modules are manufactured to order, with their enclosures and electrical designs customized to meet the agreed-upon requirements.

Connection options

Multifunctional laboratory power supplies of the DP-P Series in various versions

Image shows DP-P series laboratory power supplies, please refer to the data sheet for the size of the selected model.

RS232 and RS485 Digital Interfaces

RS232 and RS485 with Modbus RTU support are available as standard features. The open protocol facilitates integration into existing systems and the development of custom control solutions. If ordered with optional analog I/O, the RS232 connection is omitted.

LAN interface (optional)

Both RJ45 communication ports are RS485 by default. With the LAN option, one RJ45 port becomes a LAN port; the other remains RS485. The remaining ports remain unchanged.

Depending on the application, the optional LAN interface can be configured for server or client mode. It enables integration into Ethernet-based control and automation environments.

Analog I/O (optional)

The analog package combines external voltage and current setpoints with feedback of both actual values. Select a common signal standard for all four functions: 0 … 5V, 0 … 10V, or 4 … 20mA. The package replaces RS232 and can be ordered independently of the optional LAN interface.

remote-sensing input

DP-P Series models with an output current exceeding 50 A come standard with a remote measurement input. This feature allows for the compensation of line losses of up to 2 V by measuring the voltage directly at the load and adjusting it accordingly. This function is particularly useful for high currents and long connection cables.

Interlock Loop (Standard)

The 5V loop either blocks or enables the output. Upon specific request, this function can be configured at the factory as an external output ON/OFF trigger. The user cannot subsequently switch between interlock and ON/OFF trigger.

Analogue status output (standard)

The device status is transmitted via a two-wire line using two states: 0 V for an error and 5 V for normal operation.

 

ModelPriceOutput voltageOutput currentPowerDisplay resolution UDisplay resolution IResidual ripple UResidual ripple ILoad regulation ULoad regulation ILine regulation ULine regulation I
DP10H-10P4.330,00 €0 ... 1kV0 ... 10A0 ... 10kW1V10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP10H-15P5.920,00 €0 ... 1kV0 ... 15A0 ... 15kW1V10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-1HP4.140,00 €0 ... 100V0 ... 100A0 ... 10kW100mV100mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-12P-S1.900,00 €0 ... 100V0 ... 12A0 ... 1.2kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-150P5.780,00 €0 ... 100V0 ... 150A0 ... 15kW100mV100mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-15P2.210,00 €0 ... 100V0 ... 15A0 ... 1.5kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-24P2.410,00 €0 ... 100V0 ... 24A0 ... 2.4kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-30P2.510,00 €0 ... 100V0 ... 30A0 ... 3kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-40P2.800,00 €0 ... 100V0 ... 40A0 ... 4kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-50P2.970,00 €0 ... 100V0 ... 50A0 ... 5kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-60P3.240,00 €0 ... 100V0 ... 60A0 ... 6kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-6P-S1.710,00 €0 ... 100V0 ... 6A0 ... 600W100mV1mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.2% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-80P3.690,00 €0 ... 100V0 ... 80A0 ... 8kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP1H-90P3.980,00 €0 ... 100V0 ... 90A0 ... 9kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP10-10HP4.940,00 €0 ... 10V0 ... 1 kA0 ... 10kW10mV1A≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP12-1HP2.150,00 €0 ... 12V0 ... 100A0 ... 1.2kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP12-125P2.270,00 €0 ... 12V0 ... 125A0 ... 1.5kW10mV100mA≤50mVpp≤100mApp≤0.21% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP12-2HP2.450,00 €0 ... 12V0 ... 200A0 ... 2.4kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP15H-10P5.770,00 €0 ... 1.5kV0 ... 10A0 ... 15kW1V10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP15H-6P4.320,00 €0 ... 1.5kV0 ... 6.67A0 ... 10kW1V1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-1HP5.780,00 €0 ... 150V0 ... 100A0 ... 15kW100mV100mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-10P2.210,00 €0 ... 150V0 ... 10A0 ... 1.5kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-16P2.410,00 €0 ... 150V0 ... 16A0 ... 2.4kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-20P2.510,00 €0 ... 150V0 ... 20A0 ... 3kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-26-7P2.800,00 €0 ... 150V0 ... 26.7A0 ... 4kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-33-5P2.970,00 €0 ... 150V0 ... 33.5A0 ... 5kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-40P3.240,00 €0 ... 150V0 ... 40A0 ... 6kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-4P-S1.710,00 €0 ... 150V0 ... 4A0 ... 600W100mV1mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.2% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-53P3.640,00 €0 ... 150V0 ... 53A0 ... 8kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-60P3.880,00 €0 ... 150V0 ... 60A0 ... 9kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-66P4.140,00 €0 ... 150V0 ... 66A0 ... 10kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP150-8P-S1.900,00 €0 ... 150V0 ... 8A0 ... 1.2kW100mV1mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP15-1HP2.270,00 €0 ... 15V0 ... 100A0 ... 1.5kW10mV100mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP15-2HP2.650,00 €0 ... 15V0 ... 200A0 ... 3kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP15-267P2.850,00 €0 ... 15V0 ... 267A0 ... 4kW10mV100mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP15-80P2.130,00 €0 ... 15V0 ... 80A0 ... 1.2kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20H-5P4.320,00 €0 ... 2kV0 ... 5A0 ... 10kW1V1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20H-7-5P5.770,00 €0 ... 2kV0 ... 7.5A0 ... 15kW1V1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-12P2.410,00 €0 ... 200V0 ... 12A0 ... 2.4kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-15P2.510,00 €0 ... 200V0 ... 15A0 ... 3kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-20P2.800,00 €0 ... 200V0 ... 20A0 ... 4kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-25P2.970,00 €0 ... 200V0 ... 25A0 ... 5kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-30P3.420,00 €0 ... 200V0 ... 30A0 ... 6kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-3P-S1.710,00 €0 ... 200V0 ... 3A0 ... 600W100mV1mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.2% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-40P3.640,00 €0 ... 200V0 ... 40A0 ... 8kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-45P3.880,00 €0 ... 200V0 ... 45A0 ... 9kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-50P4.140,00 €0 ... 200V0 ... 50A0 ... 10kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-6P-S1.870,00 €0 ... 200V0 ... 6A0 ... 1.2kW100mV1mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-7-5P2.190,00 €0 ... 200V0 ... 7.5A0 ... 1.5kW100mV1mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP2H-75P5.640,00 €0 ... 200V0 ... 75A0 ... 15kW100mV10mA≤100mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20-120P2.450,00 €0 ... 20V0 ... 120A0 ... 2.4kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20-150P2.570,00 €0 ... 20V0 ... 150A0 ... 3kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20-250P3.020,00 €0 ... 20V0 ... 250A0 ... 5kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20-3HP3.350,00 €0 ... 20V0 ... 300A0 ... 6kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20-5HP4.330,00 €0 ... 20V0 ... 500A0 ... 10kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP20-60P-S1.760,00 €0 ... 20V0 ... 60A0 ... 1.2kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-10P2.510,00 €0 ... 300V0 ... 10A0 ... 3kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-13-3P2.800,00 €0 ... 300V0 ... 13.3A0 ... 4kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-16-7P2.970,00 €0 ... 300V0 ... 16.7A0 ... 5kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-20P3.240,00 €0 ... 300V0 ... 20A0 ... 6kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-26-7P3.640,00 €0 ... 300V0 ... 26.7A0 ... 8kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-2P-S1.710,00 €0 ... 300V0 ... 2A0 ... 600W100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.2% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-30P3.880,00 €0 ... 300V0 ... 30A0 ... 9kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-33P4.140,00 €0 ... 300V0 ... 33A0 ... 10kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-4P-S1.870,00 €0 ... 300V0 ... 4A0 ... 1.2kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-50P5.640,00 €0 ... 300V0 ... 50A0 ... 15kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-5P2.190,00 €0 ... 300V0 ... 5A0 ... 1.5kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP3H-8P2.410,00 €0 ... 300V0 ... 8A0 ... 2.4kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-1HP2.570,00 €0 ... 30V0 ... 100A0 ... 3kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-133P2.850,00 €0 ... 30V0 ... 133A0 ... 4kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-167P3.020,00 €0 ... 30V0 ... 167A0 ... 5kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-2HP3.350,00 €0 ... 30V0 ... 200A0 ... 6kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-267P3.630,00 €0 ... 30V0 ... 267A0 ... 8kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-333P4.330,00 €0 ... 30V0 ... 333A0 ... 10kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-40P-S1.900,00 €0 ... 30V0 ... 40A0 ... 1.2kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-5HP5.920,00 €0 ... 30V0 ... 500A0 ... 15kW10mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-50P2.230,00 €0 ... 30V0 ... 50A0 ... 1.5kW10mV10mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP30-80P2.450,00 €0 ... 30V0 ... 80A0 ... 2.4kW10mV10mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-1-5P-S1.770,00 €0 ... 400V0 ... 1.5A0 ... 600W100mV1mA≤200mVpp≤50mArms≤0.1% + 2 LSB≤0.2% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-10P2.800,00 €0 ... 400V0 ... 10A0 ... 4kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-12-5P2.970,00 €0 ... 400V0 ... 12.5A0 ... 5kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-15P3.240,00 €0 ... 400V0 ... 15A0 ... 6kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-20P3.640,00 €0 ... 400V0 ... 20A0 ... 8kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-22-5P3.880,00 €0 ... 400V0 ... 22.5A0 ... 9kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-25P4.140,00 €0 ... 400V0 ... 25A0 ... 10kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-3-75P2.190,00 €0 ... 400V0 ... 3.75A0 ... 1.5kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-37P5.780,00 €0 ... 400V0 ... 37A0 ... 15kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-3P-S1.870,00 €0 ... 400V0 ... 3A0 ... 1.2kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-6P2.410,00 €0 ... 400V0 ... 6A0 ... 2.4kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP4H-7-5P2.510,00 €0 ... 400V0 ... 7.5A0 ... 3kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-1HP2.850,00 €0 ... 40V0 ... 100A0 ... 4kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-125P3.020,00 €0 ... 40V0 ... 125A0 ... 5kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-150P3.300,00 €0 ... 40V0 ... 150A0 ... 6kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-2HP3.690,00 €0 ... 40V0 ... 200A0 ... 8kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-225P3.980,00 €0 ... 40V0 ... 225A0 ... 9kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-250P4.240,00 €0 ... 40V0 ... 250A0 ... 10kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-375P5.870,00 €0 ... 40V0 ... 375A0 ... 15kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-60P2.450,00 €0 ... 40V0 ... 60A0 ... 2.4kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP40-75P2.540,00 €0 ... 40V0 ... 75A0 ... 3kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-1-2P-S1.770,00 €0 ... 500V0 ... 1.2A0 ... 600W100mV1mA≤200mVpp≤50mArms≤0.1% + 2 LSB≤0.2% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-10P2.970,00 €0 ... 500V0 ... 10A0 ... 5kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-12P3.240,00 €0 ... 500V0 ... 12A0 ... 6kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-16P3.640,00 €0 ... 500V0 ... 16A0 ... 8kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-18P3.880,00 €0 ... 500V0 ... 18A0 ... 9kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-2-4P-S1.870,00 €0 ... 500V0 ... 2.4A0 ... 1.2kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-20P4.240,00 €0 ... 500V0 ... 20A0 ... 10kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-30P5.780,00 €0 ... 500V0 ... 30A0 ... 15kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-3P2.190,00 €0 ... 500V0 ... 3A0 ... 1.5kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-4-8P2.410,00 €0 ... 500V0 ... 4.8A0 ... 2.4kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-6P2.510,00 €0 ... 500V0 ... 6A0 ... 3kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP5H-8P2.800,00 €0 ... 500V0 ... 8A0 ... 4kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP50-2HP4.240,00 €0 ... 50V0 ... 200A0 ... 10kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP50-3HP5.920,00 €0 ... 50V0 ... 300A0 ... 15kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-10P3.240,00 €0 ... 600V0 ... 10A0 ... 6kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-13-3P3.640,00 €0 ... 600V0 ... 13.3A0 ... 8kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-15P3.880,00 €0 ... 600V0 ... 15A0 ... 9kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-16P4.240,00 €0 ... 600V0 ... 16A0 ... 10kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-2-5P2.190,00 €0 ... 600V0 ... 2.5A0 ... 1.5kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-25P5.780,00 €0 ... 600V0 ... 25A0 ... 15kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-2P-S1.870,00 €0 ... 600V0 ... 2A0 ... 1.2kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-4P2.410,00 €0 ... 600V0 ... 4A0 ... 2.4kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-6-7P2.800,00 €0 ... 600V0 ... 6.7A0 ... 4kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6H-8-3P2.970,00 €0 ... 600V0 ... 8.3A0 ... 5kW100mV1mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-1HP3.300,00 €0 ... 60V0 ... 100A0 ... 6kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-133P3.690,00 €0 ... 60V0 ... 133A0 ... 8kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-150P3.980,00 €0 ... 60V0 ... 150A0 ... 9kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-167P4.240,00 €0 ... 60V0 ... 167A0 ... 10kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-20P-S1.900,00 €0 ... 60V0 ... 20A0 ... 1.2kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-250P5.780,00 €0 ... 60V0 ... 250A0 ... 15kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-25P2.230,00 €0 ... 60V0 ... 25A0 ... 1.5kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-40P2.410,00 €0 ... 60V0 ... 40A0 ... 2.4kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-50P2.510,00 €0 ... 60V0 ... 50A0 ... 3kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-67P2.800,00 €0 ... 60V0 ... 67A0 ... 4kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP60-83P3.020,00 €0 ... 60V0 ... 83A0 ... 5kW10mV10mA≤50mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP6-2HP2.150,00 €0 ... 6V0 ... 200A0 ... 1.2kW1mV100mA≤50mVpp≤200mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP8H-10P3.730,00 €0 ... 800V0 ... 10A0 ... 8kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP8H-12P4.240,00 €0 ... 800V0 ... 12A0 ... 10kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP8H-18P5.780,00 €0 ... 800V0 ... 18A0 ... 15kW100mV10mA≤200mVpp≤50mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP80-125P4.240,00 €0 ... 80V0 ... 125A0 ... 10kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB
DP80-187P5.780,00 €0 ... 80V0 ... 187A0 ... 15kW10mV100mA≤50mVpp≤100mApp≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB≤0.1% + 2 LSB